A 24-hour carbon-aware dispatch model is developed for photovoltaic (PV) generation, battery storage, and demand response in distribution networks. The mixed-integer linear program minimizes electricity procurement, storage operation, demand-response compensation, PV curtailment, and carbon costs. Dispatch schedules are checked using hourly AC power flow on the IEEE 33-bus feeder, and calculated network losses are fed back into the power balance. Five scenarios distinguish storage operation, fixed and time-varying carbon emission factors, and flexible demand. Loss updates converge within four iterations in every scenario. Relative to a fixed emission factor, the time-varying factor reduces carbon emissions by 0.37% and grid purchases during high-carbon hours by 2.40%. Compared with the PV-only baseline, coordinated PV-storage-demand operation lowers total cost by 4.52%, carbon emissions by 1.74%, and peak-to-valley load spread by 6.87%, while PV utilization increases by 3.56 percentage points. These results demonstrate the value of time-resolved carbon signals and loss-consistent performance accounting under the specified case-study assumptions.
@artical{w15102026ijsea15101010,
Title = "Carbon-Aware Dispatch of PV-Storage Distribution Networks with Demand Response and AC Loss Feedback",
Journal ="International Journal of Science and Engineering Applications (IJSEA)",
Volume = "15",
Issue ="10",
Pages ="70 - 72",
Year = "2026",
Authors ="Weiliang Zhang"}